Lawton Tubes
More
Technical data
ParametersCapability
ApplicationsAir-conditioning and refrigeration
ConnectionsCopper to copper
Approved tube*: Copper tube conforming toEN 12735-1 or ASTM-B280
Fitting / tube range (inches)1/4″, 3/8″, 1/2″, 5/8″, 3/4″, 7/8″, 1″, 1 1/8″
Fitting materialRefrigerant grade copper (C12200 min 99.9% pure)
O-ringHNBR
Approved oilsPOE, PAO, PVE, AB and MO
Maximum operating and abnormal pressure48 bar / 4800 kPa / 700 psi
O-ring temperature range-40 °C to 140 °C / -40 °F to 284 °F
Burst pressure >3 x maximum operating and abnormal pressure EN 378-2>144 bar / >14400 kPa / >2100 psi
Leak tightnessHelium £ 7.5 × 10-7 Pa.m3/s at +20 °C, 10 bar
Vacuum200 microns
UL listing continuous operating temperature-40 °C to 121 °C / -40 °F to 250 °F
Compatible refrigerantsR-1234yf**, R-1234ze**, R-125, R-134a, R-290**, R-32**, R-404A, R-407A, R-407C, R-407F, R-407H, R-410A, R-417A, R-421A, R-422B, R-422D,
R-427A, R-438A, R-444A**, R-447A**, R-447B**, R-448A, R-449A, R-450A, R-452A, R-452B**,
R-452C, R-454A**, R-454B**, R-454C**,
R-457A**, R-459A**, R-507A, R-513A, R-513B, R-600A** and R-718.
* Please refer to >B< MaxiPro Technical Brochure – Tube Compatibility Table.
** When using refrigerants classified A2L (lower flammability), A2 (flammable) and A3 (higher flammability) ensure that all appropriate standards, local rules and regulations, codes of practice and by-laws are adhered to.
Back to Maxi Pro

Product Enquiry

ROMAX COMPACT TT Pipe Press

    The 'LT' logo of copper tube supplier Lawton Tubes
    Privacy Overview

    This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.